11.2.2 Immediate global alarming
The 'Immediate global alarming' setting is used to determine under which of the
following preconditions the alarm verification concept is directly and globally
alarmed:
' - (disabled)'
'Upon 2nd alarm within area'
'Upon 2nd alarm within area OR fault within station'
'Upon 2nd alarm within site'
'Upon 2nd alarm OR fault within site'
'Always (upon first alarm)'
Figure 46: Detail editor with settings for immediate global alarming
Settings for intervention
If you select the 'Upon 2nd alarm within area OR fault within station' or 'Upon 2nd
alarm OR fault within site' setting for immediate global alarming, the following
must be observed in the 'Station' settings:
The setting in the following fields must not be 'Station' for the 'Intervention' category
in the 'IC Fault' tab of the 'Disabled' detail editor:
'Immediate intervention type 'manned''
'Immediate intervention type 'unmanned''
Always select a defined setting.
Figure 47: Detail editor with settings for 'Station'
If individual devices are not to be activated using 'IC Fault', uncheck the
corresponding checkbox.