12.9 Loop sounder, loop sounder/beacon, and base
sounder
'Sounder', 'Sounder beacon', and 'Base sounder' can be allocated to the following
controls:
● In the alarming control group as:
– Internal 'Sounder'
– External 'Sounder'
● In the evac control group for:
– Universal evacuation
– 2-stage evacuation
Assigning 'Sounder'
Figure 77: 'Control' task card, alarming and evac control groups, with 'New effect dialog' window for
assigning a sounder
1. Select the 'Control' task card.
2. Depending on the application in question, open the following in the tree view:
'Alarming control group' > 'Internal sounder control' or 'External sounder control'
- OR -
'Evac control group' > 'Universal sounder evac control' or 'Phased sounder
evac control'
3. Highlight 'Effects'.
4. Select 'Assign'.
a The 'New effect dialog' window opens.
a 'Sounder' is highlighted at the left of the 'Assign dialog' window.
5. In 'Hardware tree', select the 'Sounder' channel.
6. Click on 'Assign'.
a 'Effects' is assigned to 'Sounder'.