Establishing connection from PC to FS720 network
14
327 |
Building Technologies
14.2.11.4 Site-specific configuration
For a customer-specific Ethernet network configuration, you have to set 'Type of
redundancy configuration' in the 'Site-specific'.
For the 'Site-specific' configuration, you can configure the following elements
manually:
● Suppression of ring faults
● 'Redundancy manager'
● Suppression of port faults
Proceed as described in the previous chapters to configure the individual elements.
14.3 Establishing connection from PC to FS720 network
is installed, the two routes in the table
below are entered in the PC's network settings.
Network address Network mask
↑ Gateway
address
Metric
192.168.0.0 255.255.0.0 192.168.200.1 10
192.168.0.0 255.255.0.0 192.168.201.1 10
Table 17: Persistent routes
A connection from the PC to the FS720 network can be established with the
following three variants:
● Local connection
– The PC is connected to the Ethernet connection of a ↑ standalone or
↑ SAFEDLINK station.
– The PC automatically receives an IP address.
● Connection to GAP
– The PC is connected to the 'C-WEB/LAN'.
– The PC automatically receives an IP address when the DHCP is configured
on the ↑ GAP.
● Connection to IP address
– The PC is connected to the 'C-WEB/LAN'.
– The PC's IP address must be set manually.
– If there are external routers between Cerberus-Engineering-Tool and GAP,
the necessary routers must be configured for the C-WEB/LAN and all
↑ SAFEDLINK sub-nets.
The connection can be established using the following menu items:
● For Cerberus-Engineering-Tool
– 'Commissioning' > 'Download site'
– 'Commissioning' > 'Upload site'
– 'Commissioning' > 'Upload site event memory'
– 'Commissioning' > 'Upload site log files'