'Network' task card
Network configuration
14
320 | 412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
4. In 'Secondary GAP', create a 'Route' element and enter the following values.
'Destination address': Sub-net of management station B – 10.169.30.0
'Netmask': 255.255.255.0
'Gateway': Address of 'Security module (firewall)' B – 192.168.100.11
5. In 'Ethernet sub-net', create two 'Route' elements.
6. Enter the following values in the first Route' element. Link [ 317]
'Destination address': Sub-net of management station A – 10.169.29.0
'Netmask': 255.255.255.0
'Gateway': Address of 'GAP' – 192.168.100.1
7. Enter the following values in the second Route' element:
'Destination address': Sub-net of management station B – 10.169.30.0
'Netmask': 255.255.255.0
'Gateway': Address of 'Secondary GAP' – 192.168.100.2
You will find more information about remote access with two
GAPs in document
A6V10210362. See chapter 'Applicable documents'.
See also
2 Applicable documents [ 13]
14.2.9 Configuring remote access via cRSP
To configure remote access via the 'common Remote Service Platform' (cRSP)
remote maintenance platform, you must request the following values from your
cRSP contact:
'Destination address'
'Netmask'
'Gateway'
You will find more information about remote access via cRSP in document
A6V10210362. See chapter 'Applicable documents'.