'Control' task card
Evac control group
12
192 | 412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
12.3.2.3 Assigning time control effects
l Use the 'Assign' function to assign commands and outputs as effects. Link
[ 85]
12.4 Evac control group
The 'Evac control group' element is the higher-level configuration element for all
evac. controls.
The following evac. controls can be created and configured under the 'Evac control
group' element:
'Universal sounder evac control'
'Phased sounder evac control'
'Phased voice evac control'
'Prioritized voice evac control'
12.4.1 Universal sounder evac. control
You can use a 'Universal sounder evac control' element to configure a single-
phase evac. control with standard alarm devices that can only emit one alarm tone.
The 'Universal sounder evac control' element enables an activation logic to be
configured from a combination of different causes. The element is therefore
particularly suited to evacuation applications with only one phase but with a
complex combination of different causes.