120 | 412
10.3 C-NET detector line
Adjusting the properties for a C-NET detector line in the 'Overview'
tab
'Up to 252 devices allowed per line':
This setting specifies the maximum permissible number of devices per C-NET
detector line:
● Checkbox activated: A maximum of 252 devices are permitted on the
↑ detector line.
● Checkbox deactivated: A maximum of 126 devices are permitted on the
detector line.
Properties for an C-NET detector line in the 'Details' tab
The duration of a line calibration consists of a 45
second base time plus about 1
second per installed 'Voice alarm sounder beacon/Voice al. sound. beacon base'
device on the line to be calibrated. This means a line with 252 'Voice alarm
sounder beacon/Voice al. sound. beacon base' devices can be calibrated in about
5 minutes.
Parameters Value Description
'Line calibration mode' 'Automatic without manual recalibration'
Calibration of the selected line takes
place automatically each time the line
card is restarted if a setting relevant to
power consumption has been adjusted.
Manual recalibration of the line is not
possible during active operation.
'Automatic with manual recalibration'
Calibration of the selected line takes
place automatically each time the line
card is restarted if a setting relevant to
power consumption has been adjusted.
Manual recalibration of the line is
possible during active operation.
'Manual'
Calibration of the selected line can only
be triggered manually on the 'PMI'.
' - (disabled)'
Calibration of the selected line is
deactivated.
'Events' tab
The 'Events' tab allows you to make ↑ AVC settings for line alarms. You will find
more information on this in chapter 'Alarm verification concept (AVC) [➙ 142]'.
Line card (FDnet/C-NET) FCL2001
The ↑ line card (FDnet/C-NET) FCL2001 is used for expanding the integrated C-
NET detector lines and has the same functions. Four ↑ loops or eight ↑ stubs can
be connected to a line card (FDnet/C-NET). The line card (FDnet/C-NET) is read in
automatically.