'Hardware' task card
Ethernet switch (modular) FN2012
10
138 | 412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
Configuring local ports
The configuration of the local ports for a switch integrated in a station is only
possible in the Engineering Tool.
However, the local ports of a standalone switch must be configured with the web
interface of the switch. You will find more information about this in document
'A6V10210416'. See chapter 'Applicable documents'.
Deactivated ports are not monitored for faults. Fault monitoring cannot be
configured for deactivated ports.
Do not activate fault monitoring for local ports to which a management station has
been connected. With fault monitoring for local ports to which a management
station has been connected, a fault is displayed every time the management
station is restarted.
Activate fault monitoring only for ports to which FS720 stations have been
connected.
w An 'Ethernet switch (modular, FN2012)' element is created within a station in
the 'Hardware' task card.
1. Open the 'Ethernet switch (modular, FN2012)' element.
2. Highlight the local port that you want to configure.
3. Configure the local port in the 'Overview' tab.
'Local port' element – properties in the 'Overview' tab
Property Values Description
'Port enabled' On/off The property determines whether the local port is activated or not.
Information: Deactivate any local ports on the FN2012-A1 that are
not being used in accordance with your safety requirements.
'Link monitoring' 'Disabled'
The property determines the type of connection monitoring at the
local port.
The following settings are possible:
Connection monitoring is deactivated.
Information: This is the standard setting.
'Link-down'
The system issues a message when the connection on the
port is interrupted.
Information: Activate the 'Link-down' monitoring for all ports to
which FS720 stations are connected.
'Link-up'
The system issues a message when the connection on the
port is not interrupted.