'Detection' task card
'Area'
11
144 | 412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
'Alarming type 'thermal''
This setting specifies the alarming type for thermal detectors.
'* Not used *': The alarming type for thermal detectors is not defined. The
settings for 'Alarming type 'manned'' and 'Alarming type 'unmanned'' are used.
'Global alarming only': The AVC changes to global alarming immediately.
No distinction is made between 'manned' and 'unmanned'.
These settings only apply to heat detectors (
C
-
NET
) and not to the temperature
sensors of multi-sensor fire detectors.
'Local alarming devices 'manned'' and 'Local alarming devices
'unmanned''
This setting specifies which local alarming equipment is to be activated in 'Manned
operation' or 'Unmanned operation', respectively. Activate the respective checkbox.
'Global alarming devices 'manned'' and 'Global alarming devices
'unmanned''
These settings specify which global alarming equipment is to be activated in
'Manned operation' or 'Unmanned operation', respectively. Activate the respective
checkbox.