'Control' task card
Alarming control group
12
177 |
412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
Assigning cause
NOTICE
Incorrect cause assignment for '
Activation
timeout 'manned'
' / '
Activation timeout
'unmanned''
The 'Activation timeout 'manned'' / 'Activation timeout 'unmanned'' sounder
property is only evaluated for one 'Area' element in the detection tree or for
elements within one 'Area' element.
w One or more sounders are assigned as 'Control' element effects.
w The 'Activation timeout 'manned'' property and / or 'Activation timeout
'unmanned'' is active.
Only assign one 'Area' element or elements from one 'Area' element as the
cause of the '
Control
'.
1. Select the 'Control' task card.
2. Open the 'Station' in the tree view.
3. Highlight 'Causes' in a control element of the 'Alarming control group'.
4. Open the 'Assign dialog' window.
5. In the window click an event category and select the cause from the list.
a The appropriate tree is shown in the right side of the window. The elements
that can be assigned are highlighted.
6. Select the appropriate ID No. or open the tree and select the corresponding
element.
7. Click on 'Assign'.
a 'Causes' is assigned to the element.