'Control' task card
Universal control gr
oup
12
185 |
412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
Delay times and time-out
'Activation delay': The activation of the control is delayed by the set time after
the activation condition is met.
'Deactivation delay': The deactivation of the control is delayed by the set time
after the deactivation condition is met.
'Activation timeout': The time-out is started when the control is activated. After
the expiration of the set time, the control is deactivated again automatically,
even if the conditions for activating the control are still fulfilled.
The property '
Activation timeout
' can be set only if the checkbox '
Enabled
' is
activated.
'Deactivation timeout': The time-out is started when the control is deactivated.
After the expiration of the set time, the control is activated again automatically,
even if the conditions for deactivating the control are still fulfilled.
The property '
Deactivation timeout
' can be set only if the checkbox '
Enabled
' is
activated.
The following properties can be set in the 'Details' tab:
Figure 65: Properties in the detail editor of the element 'Fire control'
'Accept commands 'Fire controls ON/OFF' from FBF'
This setting indicates whether the control can be switched off or on, respectively,
by a command on the fire brigade Person Machine Interface (PMI). If the checkbox
is checked, then all effects of the control will be switched off or on by the FBF
command for the corresponding 'Area'.
This setting is relevant only for controls in accordance with the VdS definition.
'Controls a 'door holders' application'
This property indicates whether the control is used for a fire door. If the checkbox is
activated, then fire doors will be shut automatically when the control is switched off.
This prevents fire doors from remaining open in the event of an alarm if the control
has been switched off.
If the control was created with the template 'Door holders', then the checkbox
'Controls a 'door holders' application' is activated in the default settings.