'Control' task card
Universal control group
12
190 | 412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
12.3.2.2 Creating and configuring a time control cause
Creating 'Time control cause'
1. Highlight the element 'Causes'.
2. Open the 'New element' window.
3. Select 'Add'.
a The 'Time control cause' cause element is created.
Configuring 'Time control cause'
WARNING
Activation or deactivation operations performed incorrectly in the event of a time
switchover.
If the time is put forward by one hour, activation or deactivation operations
scheduled to take place within this switchover period, e.g., between 02:00 a.m.
and 03:00 a.m., will not be performed. If the time is put back by one hour,
activation or deactivation operations scheduled to take place within this
switchover period, e.g., between 02:00 a.m. and 03:00 a.m., will be performed
twice.
If you have configured time switchover for the site, do not configure any
activation or deactivation operations to take place during the switchover
period, e.g., between 02:00
a.m. and 03:00
a.m.
NOTICE
Configuring several causes
Only one cause element may be active within a 'Time control' at any one time.
The times for activating and deactivating causes must not overlap if several
causes are configured for one 'Time control'.
If a 'Time control' has several cause elements, do not configure activation and
deactivation times that overlap.