6. Assign one or more 'PHASED sounder' elements to the 'Effects' element with
'Assign'. Alternatively, you can assign separate alarm devices for each of the
evacuation phases 'Alert' and 'Evac' with the 'ALERT sounder' and 'EVAC
sounder' elements.
Note: If you mark the 'PHASED sounder' element in the left part of dialog, then
you can only assign alarm devices in the right part that can play both a 'Alert'
tone as well as a 'Evac' tone. If you mark the 'ALERT sounder' element or the
'EVAC sounder' element, then you can only assign alarm devices in the right
part that can play either the 'Alert' tone only or the 'Evac' tone only. You will find
information on configuring the alarm devices in the chapters 'Base sounder'
and 'Alarm sounder and interbase'.
7. Configure the 'Sounder' elements in the 'Overview' tab.