12
208 | 412
'Phased voice evac control' – parameters in the 'Overview' tab
Parameters Values Description
'Custom audio library ID' Numerical input field
Adjustment range:
[0]: Standard audio library
[1...2047]: ID
user-defined audio library
The parameter determines which audio library
should be used by the devices assigned to the
control.
Note: The ID number configured here must
correspond to the imported ID numbers of the
assigned sounders in the 'Hardware' tree. If the ID
number does not match, the configuration tool
displays an error. If '0' is configured for the default
audio library, then the ID of the devices is irrelevant.
You will find more information on this in chapter
'Sounders and sounder bases (sounders, sounder
beacons, voice sounders) [➙ 126]'.
'Phased voice evac control' – parameters in the 'Details' tab
Parameters Value Description
'Accept commands
'Sounders ON/OFF'' from
FBF'
On/off
Acoustic sounders connected to the control can be
switched off at any time using the corresponding
button on the fire brigade operating panel (FBF)
when the parameter is activated.
'OFF allowed' ‒
The parameter defines whether the control can be
switched off.
The following options can be configured:
'Never' ● Never
'NOT if activated
automatically by causes'
● The control cannot be switched off if it was
activated automatically by its causes. The control
can only be switched off in the following
circumstances:
– The control is in an idle state.
– The control has been activated by a manual
command on the ↑ Person Machine
Interface.
– The control has been activated by a 'Fire
control' element.
– The control has been activated by a 'Time
control' element.
'Always' ● Always