'Control' task card
Evac control group
12
217 |
412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
14. Configure the delay times for the evacuation of this floor in the 'Table' view
using the 'Delay' parameter.
Information: The delay times specify how much time needs to elapse before
this floor is evacuated if a fire alarm is signaled on one of the floors in the table.
Information: Please see the planning documents for the building in question for
specific evacuation times. Please see the example above for possible delay
times.
15. Repeat the last two configuration steps for all other 'Phased sounder evac
control'/'Phased voice evac control' elements.
16. Assign the corresponding alarm devices or sounders to the 'Effects' element in
each 'Phased sounder evac control'/'Phased voice evac control' element.