'Control' task card
Damper control group
12
241 |
412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
Configuring LED 1 for the 'Open' (green) and 'Damper moving' (OFF)
damper states
1. Select 'LED/output | 1' and assign the LED as follows:
Go to the left of the 'New cause dialog' and select the ' --Damper changing
position' event under 'Events 'Information''.
On the right-hand side, select the required 'Fire damper output/supervised'
from the control tree: 'Control tree' > 'Station' > 'Damper control group' >
'Fire damper control' > 'Effects' > 'Fire damper output/supervised'.
Click on 'Assign'.
2. Select the cause element that has been created under 'LED/output | 1' and set
the following properties on the 'Overview' tab:
Colour: 'Green'
Priority: '01 (highest)'
LED mode: 'Inactive: On / active: Off'
Configuring LED 1 for the 'Closed' damper state
1. Assign 'LED/output | 1' to another cause as follows:
Go to the left of the 'New cause dialog' and select the ' --Technical
message: confirmed' event under 'Events 'Technical message''.
On the right-hand side, select the same 'Fire damper output/supervised' as
for the first assignment from the control tree: 'Control tree' > 'Station' >
'Damper control group' > 'Fire damper control' > 'Effects' > 'Fire damper
output/supervised'.
Click on 'Assign'.
2. Select the cause element that has been created under 'LED/output | 1' and set
the following properties on the 'Overview' tab:
Colour: 'Red'
Priority: '02'
LED mode: 'Inactive: Off / active: On'
Configuring LED 1 for the 'Timeout/Fault/Unexpectedly
open/Unexpectedly closed' (off) damper state
1. Assign 'LED/output | 1' to another cause as follows:
Go to the left of the 'New cause dialog' and select the 'All faults' event
under 'Events 'Fault''.
On the right-hand side, select the same 'Fire damper output/supervised' as
for the first assignment from the control tree: 'Control tree' > 'Station' >
'Damper control group' > 'Fire damper control' > 'Effects' > 'Fire damper
output/supervised'.
Click on 'Assign'.
2. Select the cause element that has been created under 'LED/output | 1' and set
the following properties on the 'Overview' tab:
Colour: 'Green'
Priority: '03'
LED mode: 'Inactive: On / active: Off'