Extinguishing standard interface SST [DE]
12
243 |
Building Technologies
Creating an output for extinguishing actuation
An output of the input/output module is used to actuate the extinguishing process
via the extinguishing control system. The command for the extinguishing actuation
is give by detector zone(s) of the fire control panel.
Figure 70: 'New cause dialog, Assign dialog' window for assigning the cause for the extinguishing
actuation
Figure 71: 'New cause dialog, Assign dialog' window for assigning the effect for the extinguishing
actuation
To assign the cause and ↑ effect of the extinguishing actuation, proceed as
follows:
1. Select the 'Control' task card.
2. Highlight the ↑ 'Station' in the tree view and create a ↑ 'Fire control group'
element and a 'Fire control' element below this.
3. Select 'Assign'.
a The 'New cause dialog, Assign dialog' window opens.
4. Highlight 'Causes' and, in the 'New cause dialog' window, highlight ' ----All
autom. Fire ALARMS' in the 'Event' list.
5. Select the relevant automatic ↑ zone(s) and click on 'Assign'.
a 'Causes' is assigned to the zone(s).
6. Highlight 'Fire control' and set the conditions for extinguishing activation in the
detail editor, 'Overview' button.
7. Highlight 'Effects' and, in the 'New effect dialog' window, highlight 'Output/NO
confirmation'.
8. Select the relevant 'Output' of input/output module FDCIO224 and click on
'Assign'.
a 'Effects' is assigned to the 'Output'.