'Control' task card
Extinguishing standard interface SST [DE]
12
245 |
412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
Creating a 'Fault extinguish.' input
Figure 73: 'New element' window for creating the technical zone for 'Fault extinguish.'
Figure 74: 'Assign dialog' window for assigning the 'Fault extinguish.' input
To create and assign the 'Fault extinguish.' input, proceed as follows:
1. Highlight 'Section'.
2. In the 'New element' window, select the zone 'Technical zone' in the 'Type:'
field and 'Fault extinguishing system' in the 'Template:' field, and click on 'Add'.
3. Highlight the 'Technical zone' zone.
4. Open the 'Assign dialog' window and highlight 'Input'.
a The 'Hardware tree' is shown. The elements that can be assigned are
highlighted.
5. Select the relevant 'Input' of input/output module FDCIO224 and click on
'Assign'.
a 'Technical zone' is assigned to the 'Input'.
Creating fire brigade operating panel (FBF)
You will find more information in chapter 'Fire brigade periphery [DE] [ 294]'.