Global BACnet configuration
14
331 |
Building Technologies
Figure 151: Global BACnet settings
The following values in the detail editor must match the settings of the
↑ management station:
The BACnet device ID consists of the 'Device' area type and the instance
number.
● 'Address range, lower limit'/'Address range, upper limit':
Range for instance number values for identifying the FS720 stations in BACnet.
The address range is exported in SiB-X format.
● 'BACnet character set':
Character set that is used in the BACnet protocol for text strings. FS720
functions internally with Unicode in UTF-8 format.
Selectable character sets:
– UTF 8
– UCS 2 (Unicode 2 bytes)
– ISO Latin 1 (8 bits)
14.7.1.1 BACnet UDP port
The 'BACnet UDP port' is in the tree view of the 'Network' task card in the element
'Global system configuration' > 'FS720 network configuration' > 'Ethernet sub-net' >
'Connections'.
Figure 152: BACnet UDP port
If you have configured an unnetworked '
'Connections' is missing.
You can generate the element 'Connections' by creating an additional 'Ethernet
station' in the hardware tree. The element 'Connections' remains in place, even if
you delete the newly created 'Ethernet station' again.