Extinguishing
Configuring the extinguishing terminal
16
383 |
412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
6. Assign one or several 'Local event' elements to the required LED lights in the
'LED' zone with 'New element'.
7. Configure the assigned 'Local event' elements.
You will find the allocation of the hardware ID for the physical LEDs on the
extinguishing terminal in a separate section further down in this chapter.
8. Set the customer texts for the required buttons in the 'Overview' tab.
9. Assign one or several actions to the required LED lights in the 'Keys' zone with
'Assign'. Alternatively, you can also create actions with 'New element' under the
button in question.
10. Configure the assigned 'Action' elements. You will find the assignment of the
hardware ID to the physical LEDs on the extinguishing terminals in a separate
section further down in this chapter.