EasyManuals Logo

Siemens FUS1010 User Manual

Siemens FUS1010
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #194 background imageLoading...
Page #194 background image
Appendix
A.2 I/O Connections and Wiring
FUS1010 IP65 NEMA 4X & IP66 NEMA 7
Operating Instructions, 01/2013, A5E02951520-AC
193
Table A- 10 Open Collector User Resistor Recommendations
User Supply
Voltage (VDC)
External Resistor
(Ohms)
Expected
Current Draw (mA)
Recommended Resistor
Wattage (Watts)
5 270 18.5 1/2
9 510 17.6 1/2
12 680 17.6 1/2
18 1000 18 3/4
24 1500 16 1
28 1800 15.5 1 1/4
36 2400 15 1 1/4
Note
TB2-9 and TB2-11 are Open Collector Outputs that require external pull-up resistors for
operation. See table for External Supply Voltage and suggested resistor value and ratings.
Maximum current into the transistor is 100mA. Maximum Voltage is +36 VDC.
NOTICE
Transistor Damage
Negative voltages with respect to ground will permanently damage transistors.
Use caution when applying power to circuit boards.