RUGGEDCOM ROS
User Guide
Chapter 3
Device Management
Viewing Statistics for Specific Ethernet Ports 61
Parameter Description
CRCAlignErrors Synopsis: 0 to 4294967295
The number of packets received which meet all the following conditions:
• Packet data length is between 64 and 1536 octets inclusive.
• Packet has invalid CRC.
• Collision Event has not been detected.
• Late Collision Event has not been detected.
OversizePkts Synopsis: 0 to 4294967295
The number of packets received with data length greater than 1536 octets and valid CRC.
Fragments Synopsis: 0 to 4294967295
The number of packets received which meet all the following conditions:
• Packet data length is less than 64 octets, or packet without SFD and is less than 64
octets in length.
• Collision Event has not been detected.
• Late Collision Event has not been detected.
• Packet has invalid CRC.
Jabbers Synopsis: 0 to 4294967295
The number of packets which meet all the following conditions:
• Packet data length is greater that 1536 octets.
• Packet has invalid CRC.
Collisions Synopsis: 0 to 4294967295
The number of received packets for which Collision Event has been detected.
LateCollisions Synopsis: 0 to 4294967295
The number of received packets for which Late Collision Event has been detected.
Pkt64Octets Synopsis: 0 to 4294967295
The number of received and transmitted packets with size of 64 octets. This includes
received and transmitted packets as well as dropped and local received packets. This does
not include rejected received packets.
Pkt65to127Octets Synopsis: 0 to 4294967295
The number of received and transmitted packets with size of 65 to 127 octets. This includes
received and transmitted packets as well as dropped and local received packets. This does
not include rejected received packets.
Pkt128to255Octets Synopsis: 0 to 4294967295
The number of received and transmitted packets with size of 128 to 257 octets. This
includes received and transmitted packets as well as dropped and local received packets.
This does not include rejected received packets.
Pkt256to511Octets Synopsis: 0 to 4294967295
The number of received and transmitted packets with size of 256 to 511 octets. This
includes received and transmitted packets as well as dropped and local received packets.
This does not include rejected received packets.
Pkt512to1023Octets Synopsis: 0 to 4294967295
The number of received and transmitted packets with size of 512 to 1023 octets. This
includes received and transmitted packets as well as dropped and local received packets.
This does not include rejected received packets.
Pkt1024to1536Octets Synopsis: 0 to 4294967295

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RUGGEDCOM ROS and is the answer not in the manual?

Siemens RUGGEDCOM ROS Specifications

General IconGeneral
BrandSiemens
ModelRUGGEDCOM ROS
CategoryControl Unit
LanguageEnglish

Related product manuals