Power Modules
4.2 Blocksize Power Modules (PM240-2)
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
103
Note
Mounting instructions
•
Please refer to the notes for installing Power Modules in Section Safety information for
240-2 Power Modules (Page 90).
You must mount the PM240-2 Push Through Power Modules on an unpainted metal
surface in order to comply with EMC requirements.
To be able to mount PM240-2 Push Through Power Modules, the wall thickness of the
cabinet must be ≤ 3.5 mm.
Note
Installation frame for push through units
An installation frame should be used when push through units are installed in the cabinet.
You can find more information about the installation frame in Section
Mounting frame
401).
This mounting frame includes the necessary seals and frame to ensure compliance with
degree of protection IP54.
If you do not use the mounting frames, you must ensure that the required degree of
protection is
complied with using other appropriate measures.