Power Modules
4.2 Blocksize Power Modules (PM240-2)
AC Drive
106 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
4.2.6
Technical data
Note
Degree of protection of PM240-2 Power Modules
The degree of protection of the PM240
-2 Power Modules is IP20.
When Push Through Power Modules are installed in a cabinet with degree of protection IP54
using a suitable mounting frame and seals, the Power Modules also comply with this degree
of protection.
According to UL the Push Through units only fulfill the requirements of an open type
component.
4.2.6.1
200 V Power Modules
Table 4- 8 Technical data of the PM240-2, FSA (200 V)
Line voltage 1-phase/3-phase 200 … 240 VAC ± 10%
Internal
Push-through
Order number
without integrated line filter
with integrated line filter
6SL3210
1PB13-0UL0
1PB13-0AL0
6SL3210
1PB13-8UL0
1PB13-8AL0
6SL3211
1PB13-8UL0
1PB13-8AL0
Output current
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
Peak current l
max
A
A
A
A
3,0
2,3
3,3
4,6
3,9
3,0
4,3
6,0
3,9
3,0
4,3
6,0
Type rating
1)
based on I
n
based on I
H
kW
kW
0,55
0,37
0,75
0,55
0,75
0,55
Rated pulse frequency
kHz
4
4
4
Power loss
kW
0,04
0,04
0,04
4)
Cooling air requirement
m
3
/s
0,005
0,005
0,005
24 VDC supply
for the Control Unit
A
1,0
1,0
1,0
Rated input current
2)
with/without integrated line reactor
A 7,5 9,6 9,6
Class J UL fuses
Rated current
Short-circuit current rating
SCCR
A
kA
10
65
15
65
15
65
NH fuses
IEC 60947
Rated current
A
3NA3 803
10
3NA3 805
16
3NA3 805
16
Resistance value
of the external
braking resistor
Ω ≥ 200 ≥ 200 ≥ 200