10.9 Information on control cabinet cooling
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
443
10.9
Information on control cabinet cooling
10.9.1
General
Electrical cabinets can be cooled, using among other things with the following:
filtered fans
heat exchangers or
cooling units.
The decision in favor of one of these methods depends on the prevailing ambient conditions
and the cooling power required.
The air routing inside the control cabinet and the ventilation clearances specified here, must
be carefully observed. Other components or cables must not be installed/routed in these
areas.
You must comply with the following specifications when installing SINAMICS components:
Cooling clearance
Cable routing
Air guidance, air-conditioner
Table 10- 20 Ventilation clearances around the components
Component
Clearance above and
below
in mm and (inches)
Lateral clearance
in mm and (inches)
Clearance in front of
the component
CU310-2 DP
50 (1.97)
CU310-2 PN
50 (1.97)
CUA31
50 (1.97)
SMCxx
50 (1.97)
Line filter
100 (3.93)
Line reactor
100 (3.93)
PM240-2 Blocksize, frame size FSA … FSC Above: 80 (3.15)
Below: 100 (3.93)
1 (0,04)
PM340 Blocksize, frame size FSA
100 (3.93)
30 (1.18)
1)
PM340 Blocksize, frame size FSB
100 (3.93)
40 (1.57)
1)
30 (1.18)
PM340 Blocksize, frame size FSC
125 (4.92)
50 (1.97)
1)
30 (1.18)
PM340 Blocksize, frame sizes FSD and FSE
300 (11.81)
30 (1.18)
PM340 Blocksize, frame size FSF
350 (13.77)
30 (1.18)
1)
The PM340 Power Modules can be mounted side by side without base components up to an ambient temperature of
40° C. In combination with base components and at ambient temperatures of 40° C to 55° C, the specified lateral
minimum clearances must be observed. Where combinations of different frame sizes are concerned, the longer of the
two clearances shall apply.