Power Modules
4.3 Power Modules Blocksize (PM340)
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
145
Danger to life due to electric shock due to exposed terminals
Touching live components results in death or severe injury.
• Only operate the Power Module with the terminal cover closed
Power Modules Blocksize, 1-ph. AC
Table 4- 23 Technical data PM340, FSA (1-phase AC)
Line voltage 1-phase 200 … 240 VAC ± 10%
PM340 with integrated line filter
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
A
A
A
0,9
0,8
1,4
2,3
2,0
3,3
3,9
3,4
5,5
n
1)
3
Sound pressure level LpA (1 m)
dB < 45 < 45 < 45
2)
with/without integrated line reactor
Rated current
Short-circuit current rating
A
6
10
15
Circuit-breaker type designation
EN 60947
5SJ4206-7HG41
5SJ4210-7HG41
5SJ4216-7HG41
Circuit-breaker type designation
UL489 / CSA C22.2 No. 5-02
Rated current
Rated short-circuit current SCCR
A
5SJ4206-7HG41
6
5SJ4210-7HG41
10
5SJ4216-7HG41
16
of the external