Motor-side power components
6.1 Blocksize
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
227
6.1.1.5
Electrical connection
Electrical connection of PM240-2 Power Modules
Note
Approved cables
Use only 75° C copper cables.
Table 6- 12 Securing the connection cables to the motor reactor
Frame size
Terminal connection
PE connection
Max. cross-section that
can be connected
Tightening torque
Fastening
Tightening torque
FSA
4 mm
2
0.6 … 0.8 Nm
M4 screw
3 Nm
FSB
10 mm
2
1.5 … 1.8 Nm
M5 screw
5 Nm
FSC
16 mm
2
2.0 … 4.0 Nm
M5 screw
5 Nm
Electrical connection of PM340 Power Module
PE connection
Motor reactor
Figure 6-13 Electrical connection