Control Units, Control Unit Adapters and operating components
7.3 Control Unit CU310-2 PN (PROFINET)
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
279
Table 7- 14 Measuring sockets T0, T1, T2
Voltage: 0 … V
Resolution: 8 bits
Load current: max. 3 mA
Continued-short-circuit-proof
The reference potential is terminal M
GND Ground
The measuring sockets are only suitable for multiple-spring wire plugs with a diameter of 2 mm.
Note
Measuring sockets support commissioning and diagnosis. It must not be connected for
normal operation.
DIP switch S5 is used to switch the analog input between voltage input or current input. It is
located under the blanking cover (see CU310-2 PN Interface Overview (Page 263).)
Table 7- 15 DIP switch S5 - switchover between voltage/current
Switchover between voltage (U) / current (I)
S5.1 Not assigned
The DIAG pushbutton is reserved for service functions.
Pressing the RESET button restarts the CU310-2 PN after expiry of a preset time. A data
backup is run at the same time. This means that all the settings are retained.