Mains connection and line-side power components
3.8 Line reactors
AC Drive
72 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Table 3- 17 Technical data of Blocksize line reactors PM240-2
Matching Power
Modules
1)
Line voltage 1-phase 200 VAC -10% to 240 VAC +10%:
6SL3210-
1PB13-0xL0
1PB13-8xL0
6SL3210-
1PB15-5xL0
1PB17-4xL0
1PB21-0xL0
6SL3211-
6SL3210-
1PB21-4xL0
1PB21-8xL0
6SL3211-
1PB21-8xL0
6SL3210-
1PC22-2xL0
1PC22-8xL0
6SL3211-
1PC22-2xL0
Line voltage 3-phase 380 VAC -10% to 480 VAC +10%:
6SL3210-
1PE11-8xL1
1PE12-3xL1
1PE13-2xL1
6SL3210-
1PE14-3xL1
1PE16-1xL1
1PE18-0xL1
6SL3211-
6SL3210-
1PE21-1xL0
1PE21-4xL0
1PE21-8xL0
6SL3211-
6SL3210-
1PE22-7xL0
1PE23-3xL0
6SL3211-
1PE23-3xL0
Unit rating of the Power
Module
kW 0,55 … 1,1 1,5 … 4,0 4,0 … 7,5 11 … 15
Line/load connection
1L1, 1L2,1L3
2L1, 2L2, 2L3
Max. connectable
cross-section:
2.5 mm
2
Tightening torque:
Max. connectable
cross-section:
2.5 mm
2
Tightening torque:
Max. connectable
cross-section: 6
mm
2
Tightening torque:
Max. connectable
cross-section: 16
mm
2
Tightening torque:
PE connection Type: M4 bolts
Tightening torque: 3
Type: M4 bolts
Tightening torque: 3
Type: M5 bolts
Tightening torque: 5
Type: M5 bolts
Tightening torque: 5
1)
x = A: Power Module with integrated line filter, x = U: Power Module without integrated line filter