Control Units, Control Unit Adapters and operating components
7.3 Control Unit CU310-2 PN (PROFINET)
AC Drive
278 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
7.3.2.11
X150 P1/P2 PROFINET
Table 7- 12 X150 P1 and X150 P2 PROFINET
Pin
Signal name
Technical data
1
RXP
Receive data +
2
RXN
Receive data -
3
TXP
Transmit data +
4
Reserved, do not use
-
5
Reserved, do not use
-
6
TXN
Transmit data -
7
Reserved, do not use
-
8
Reserved, do not use
-
Connector type:
RJ45 socket
Data rate:
100 Mbits or 10 Mbits
Note
The PROFINET interfaces support Auto MDI(X). It is there
fore possible to use both crossed
and uncrossed cables to connect the devices.
For diagnostic purposes, the two PROFINET interfaces are each equipped with a green and
a yellow LED. The table shows the status information these indicate.
Table 7- 13 LED states on the X150 P1/P2 PROFINET interface
LED
Color
Status
Description
Link port
-
OFF
Missing or faulty link
Green Continuous
light
10 or 100 Mbit link available
Activity port
-
OFF
No activity
Yellow
Flashing
Data is being received or sent at port x