Cabinet design and EMC for components, Blocksize format
10.6 Connection Methods
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
435
Current-carrying capacity and derating factors for power cables and signal
cables
The current-carrying capacity of PVC/PUR-insulated copper cables is specified for routing
types B1, B2 and C under continuous operating conditions in the table with reference to an
ambient air temperature of 40 °C. For other ambient temperatures, the values must be
corrected by the factors listed in the "Derating factors for deviating ambient temperatures"
table.
Table 10- 12 Current carrying capacity according to EN 60204-1 for 40 °C ambient temperature
Current carrying capacity, effective; AC 50/60 Hz or DC
For routing type
Table 10- 13 Current carrying capacity according to IEC 60364-5-52 for 40 °C ambient temperature
Current carrying capacity, effective; AC 50/60 Hz or DC
For routing type
185 – – 392
> 185 Values must be taken