Cabinet design and EMC for components, Blocksize format
10.9 Information on control cabinet cooling
AC Drive
450 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Power loss for Power Modules
Table 10- 23 Overview of power loss during rated operation for Power Modules
Rated output current I
rated
/Unit rating
based on I
rated
7.5 A / 0.55 kW FSA 1-phase/3-phase 200 …
kW 0,04
9.6 A / 0.75 kW FSA 1-phase/3-phase 200 …
kW 0,04
13.5 A / 1.1 kW FSB 1-phase/3-phase 200 …
kW 0,05
1801 A / 1.5 kW FSB 1-phase/3-phase 200 …
kW 0,07
24.0 A / 2.2 kW FSB 1-phase/3-phase 200 …
kW 0,12
35.9 A / 3.0 kW FSC 1-phase/3-phase 200 …
kW 0,14
43.0 A / 4.0 kW FSC 1-phase/3-phase 200 …
kW 0,18
2.3 A / 0.55 kW FSA 3-phase 380 ... 480 VAC kW 0,04
4.1 A / 1.1 kW FSA 3-phase 380 ... 480 VAC kW 0,04
PM240-2 Blocksize Push Through
9.6 A / 0.75 kW FSA 1-phase/3-phase 200 …
kW 0,04
24.0 A / 2.2 kW FSB 1-phase/3-phase 200 …
kW 0,12
43.0 A / 4.0 kW FSC 1-phase/3-phase 200 …
kW 0,18
39.9 A / 15.0 kW FSC 3-phase 380 ... 480 VAC kW 0,37