Siemens S120 - 3 Mains Connection and Line-Side Power Components; Introduction

Siemens S120
500 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
39
Mains connection and line-side power components
3
3.1
Introduction
The following line-side components should be used to connect a SINAMICS drive line-up to
the supply network:
Line disconnector
Overcurrent protection device (line fuses or circuit-breaker)
Line contactor (this is required for electrical isolation)
Line filter (optional)
Line reactor (optional)
The possible supply voltages for the drive line-up are:
1-phase 200 VAC to 240 VAC ± 10%
3-phase 200 VAC to 240 VAC ± 10%
3-phase 380 VAC to 480 VAC ± 10%
The following line reactor variants are available:
4 versions for PM240-2 Blocksize format Power Modules, frame sizes FSA to FSC
(stand-alone)
3 versions for PM340 Blocksize format Power Modules, frame sizes FSA to FSC (base)
5 versions for PM340 Blocksize format Power Modules, frame sizes FSD to FSF (3 base
and 2 standalone)
4 versions for chassis format
The following line filter variants are available:
Integrated
External
Base
Stand-alone