Loading...
Motor-side power components
6.2 Chassis
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
243
6.2.3.4
Connecting the dv/dt filter plus Voltage Peak Limiter
Figure 6-18 Connecting the dV/dt filter plus Voltage Peak Limiter
Cable cross-sections
Table 6- 22 Cable cross-sections for connections between a dV/dt filter and Power Module
dV/dt filter plus Voltage Peak
Limiter
Connection to the DC link
(DCPS / DCNS)
[mm²]
Connection between a dV/dt
reactor and Voltage Peak
Limiter
(1U2, 1V2, 1W2) [mm²]
6SL3000-2DE32-6AA0
35
10
6SL3000-2DE35-0AA0
70
16