Control Units, Control Unit Adapters and operating components
7.4 Control Unit CU310-2 DP (PROFIBUS)
AC Drive
312 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
7.4.4.3
Behavior of the LEDs in the operating state
Table 7- 39 Description of the LEDs during operation of the CU310-2 DP
LED
Color
State
Description / cause
Remedy
RDY
(READY)
- OFF The electronics power supply is missing or outside
the permissible tolerance range.
Check the power
supply
Green
Continuous light The unit is ready for operation.
Cyclic DRIVE-CLiQ communication is in progress.
-
Flashing light
0.5 Hz
Commissioning/reset -
Flashing light 2
Hz
Writing to the memory card. -
Red Flashing light
2 Hz
General fault Check parameter
assignment/configurati
on
Red/green Flashing light
0.5 Hz
The control unit is ready for operation, but there
are no software licenses.
Install the missing
licenses.
Orange
Flashing light
0.5 Hz
Updating the firmware of the DRIVE-CLiQ
components.
-
Flashing light
2 Hz
DRIVE-CLiQ component firmware update
completed. Waiting for POWER ON of the
corresponding components.
Switch on the
component.
Green/oran
ge
or
red/orange
Flashing light
2 Hz
Recognition of the component via LED is activated
(see SINAMICS S120/S150 List Manual).
Note:
Both possibilities depend on the status of the LED
when activating.
-
COM - OFF Cyclic communication is not (yet) running.
Note:
The PROFIdrive is ready for communication when
the Control Unit is ready for operation (see LED:
RDY).
-
Green
Continuous light
Cyclic communication is taking place.
-
Flashing light
0.5 Hz
Cyclic communication is not fully established yet.
Possible causes:
- The controller is not transmitting any setpoints.
-
In isochronous mode, the controller is not sending
a GC (Global Control) or is sending a defective
GC.
-
Red
Flashing light
0.5 Hz
The PROFIBUS master is sending a faulty
parameter assignment or the configuration file is
corrupted.
Modify the
configuration between
master/controller and
control unit.
Flashing light
2 Hz
Cyclic bus communication has been interrupted or
could not be established.
Rectify the fault in bus
communication.