System overview
2.5 System data
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
35
Table 2- 1 Electrical data
Blocksize format units 1-phase 200 … 240 VAC ±10%
3-phase 200 … 240 VAC ±10%
3-phase 380 … 480 VAC ±10%
3-phase 380 … 480 VAC ±10%
Blocksize format units 4 kHz
At higher pulse frequencies, the corresponding characteristic for
current derating must be taken into consideration.
Chassis format units 2 kHz
At higher pulse frequencies, the corresponding characteristic for
current derating must be taken into consideration.
Blocksize format units 0 V to 0.74 line supply voltage for devices with 1-phase 200 …
240 VAC
0 V to 0.95 line supply voltage for devices with 3-phase 200 …
240 VAC
0 V to 0.95 line supply voltage for devices with 3-phase 380 …
0 V to line supply voltage for 3-phase 380 VAC to 480 VAC units
24 VDC -15/+20%
1)
, Safety extra-low voltage PELV or SELV
(see Chapter 24 V DC Supply Voltage (Page 422))
Short-circuit current rating
SCCR according to
UL508C (up to 600 V)
• 1.1 … 447 kW: 65 kA
• 448 … 671 kW: 84 kA
• 672 … 1193 kW: 170 kA
• ≥ 1194 kW: 200 kA
For Blocksize and Chassis components, UL certification applies only in
conjunction with the fuses prescribed by Siemens and not with other
types or just with circuit-breakers.
Electromagnetic compatibility
according to EN 61800-3
Category C3 (option)
Category C2 (option)
Category C1 (option)
for systems implemented in conformance with the documentation
1)
If a motor holding brake is used, restricted voltage tolerances (24 V ±10%) may have to be taken into account.