System overview
2.5 System data
AC Drive
36 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Table 2- 2 Environmental conditions
Degree of protection
IPXXB according to EN 60529, open type according to UL 508
Protection class, line supply circuits
Electronic circuits
I (with protective conductor connection)
safety extra-low voltage PELV / SELV
Type of cooling
Internal air cooling,
power units with forced air cooling using an integrated fan
Permissible cooling medium temperature (air)
and installation altitude in operation
0° C to +40° C and an installation altitude of up to 1000 m without
derating,
>40° C to +55° C, see derating characteristics
Installation altitude >1000 m to 4000 m refer to the characteristic for
current derating or
reduction of the ambient temperature by 3.5 K per 500 m.
Chemically active substances
Long-term storage in the transport packaging
Class 1C2 according to EN 60721-3-1
Transport in the transport packaging
Class 2C2 according to EN 60721-3-2
Operation
Class 3C2 according to EN 60721-3-3
Biological environmental conditions:
Storage in the transport packaging Class 1B1 according to EN 60721-3-1
Transport in the transport packaging
Class 2B1 according to EN 60721-3-2
Operation
Class 3B1 according to EN 60721-3-3
Vibratory load
Long-term storage in the transport packaging
Class 1M2 according to EN 60721-3-1
Transport in the transport packaging
Class 2M3 according to EN 60721-3-2
Shock load
Long-term storage in the transport packaging
Class 1M2 according to EN 60721-3-1
Transport in the transport packaging
Class 2M3 according to EN 60721-3-2
Operation
Class 2M2 according to EN 60721-3-2
Blocksize format FSA to FSB
Test values: 147 m/s
2
(15g)/11 ms
Blocksize format FSC to FSF
Test values: 49 m/s
2
(5g)/30 ms
Chassis format
Test values: 98 m/s
2
(10g)/20 ms
Climatic ambient conditions
Long-term storage in the transport packaging Class 1K4 according to EN 60721-3-1
Temperature: -25° C to +55° C
Transport in the transport packaging Class 2K4 according to EN 60721-3-2
Temperature: -40° C to +70° C
Operation Class 3K3 according to EN 60721-3-3
Temperature +0° C to +40° C
Relative humidity: 5% to 90%
Oil mist, salt mist, ice formation, condensation, dripping water, spray,
splash water, water jets are not permitted
Table 2- 3 Certificates
Declarations of Conformity
CE (Low-Voltage and EMC Directive)
Approvals cULus
cURus

Table of Contents