Motor-side power components
6.2 Chassis
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
255
Table 6- 28 Technical data, dV/dt filter compact plus Voltage Peak Limiter
Suitable for Power Module (unit rating) 6SL3310- 1TE32-1AAx (110 kW)
1TE32-6AAx (132 kW)
1TE33-1AAx (160 kW)
1TE33-8AAx (200 kW)
Power loss
- at 50 Hz
- at 60 Hz
kW
kW
0,210
0,215
0,290
0,296
Connections
- 1U1/1V1/1W1
- DCPS/DCNS
- 1U2/1V2/1W2
For M10 stud
For M8 screw
For M10 stud
For M10 stud
For M8 screw
For M10 stud
Max. permissible cable length between
m 100 (shielded)
Dimensions
Width
Height
Depth
mm
mm
mm
310
283
238
350
317
260