Supplementary system components and encoder system integration
8.3 Safe Brake Adapter optional module
AC Drive
388 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
8.3.3.4
X14 load connection
Table 8- 27 X14 load connection
Terminal
Signal
Technical data
X14.1
BR L
Supply voltage: AC 230 V
Current consumption: 2 A
X14.2
BR N
Max. connectable cross-section: 2.5 mm
2
WARNING
Fire hazard due to overheating when permissible cable lengths are exceeded
Excessively long power cables can cause overheating of components with resulting fire and
smoke development.
The maximum permissible cable length of 300 m between the Safe Brake Adapter 230
V AC and the brake must not be exceeded.
Information for precise calculation of the maximum cable length can be found in the
Configuration Manual: SINAMICS-Low Voltage.
8.3.3.5
X15 fast de-energization
Table 8- 28 X15 fast de-energization
Terminal
Signal
Technical data
X15.1
AUX 1
Supply voltage: AC 230 V
Current consumption
X15.2
AUX 2
Max. connectable cross-section: 2.5 mm
2