DC link components
5.2 Chassis
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
197
Braking resistor connection X1
Table 5- 8 Braking resistor connection
Braking resistor connection R+
Break resistor connection R-
Max. cross-section that can be connected: 50 mm
2
X21 digital inputs/outputs
Table 5- 9 Terminal block X21
Shield connection for terminal 2 ... 6
Low signal level: -3 … 5 V
High signal level: 15 … 30 V
Current consumption: 2 … 15 mA
3 DI inhibit input
Voltage: 24 V DC
Load current: 0.5 … 0.6 A
6 +24 V Voltage: 18 ... 30 V
Typical current consumption (own current consumption): 10 mA at 24 V
Max. connectable cross-section 1.5 mm
2
1)
DI: Digital input; DO: Digital output
Note
When the Braking Module is in the installed state, the
individual terminals on its X21 terminal
block are positioned as follows: terminal "1" is at the rear, terminal "6" at the front.
Note
Applying a high signal to terminal X21.3 inhibits the Braking Module. On a falling edge,
pending error signals are a
cknowledged.
Note
You will find setting instructions for wiring the signals in the SINAMICS S120 Function
Manual.