Cabinet design and EMC for components, Blocksize format
10.6 Connection Methods
AC Drive
436 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Routing types
B1 Cables in conduits or installation ducts
B2 Multi-core cables in conduits or installation ducts
C Cables along walls/panels, without conduits or installation ducts
Table 10- 14 Derating factors for deviating ambient temperatures
Ambient air temperature [°C]
Derating factor according to EN 60204-1, Table D1
30
1,15
35
1,08
40
1,00
45
0,91
50
0,82
55
0,71
60
0,58