EasyManua.ls Logo

Siemens S120 - Page 146

Siemens S120
500 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Power Modules
4.3 Power Modules Blocksize (PM340)
AC Drive
146 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Line voltage 1-phase 200240 VAC ± 10%
PM340
6SL3210
1SB11-0UA0
1SB12-3UA0
1SB14-0UA0
PM340 with integrated line filter
6SL3210
1SB11-0AA0
1SB12-3AA0
1SB14-0AA0
Max. cable length
to braking resistor
m
15
15
15
Line supply connectionL, N
Screw terminals for cable cross-sections 1.0 to 2.5 mm
2
Motor connection U2, V2, W2
DC-link connection, connection for
braking resistorDCP/R1, DCN, R2
PE connection
At the housing with M4 screw
Max. motor cable length
3)
(without external options)
m 50 (shielded)
75 (unshielded)
Degree of protection
IP20 or IPXXB
Weight
kg
1,2
1,3
1,3
1)
Rated output of a typical standard induction motor at 230 V.
2)
The i
nput current depends on the motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
3)
Max. motor cable length 15 m (shielded) for PM340 Power Modules with integrated line filter to maintain the limit values
of EN 61800-3 Category C2.

Table of Contents

Other manuals for Siemens S120

Related product manuals