Power Modules
4.2 Blocksize Power Modules (PM240-2)
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
107
Line voltage 1-phase/3-phase 200 … 240 VAC ± 10%
Order number
without integrated line filter
with integrated line filter
6SL3210–
1PB13-0UL0
1PB13-0AL0
6SL3210–
1PB13-8UL0
1PB13-8AL0
6SL3211–
1PB13-8UL0
1PB13-8AL0
Max. cable length
to braking resistor
Line supply connection L1, L2, PE
Screw-type terminals
cable cross-section: 1.5 … 2.5 mm
2
Tightening torque: 0.5 Nm
Motor connection U2, V2, W2
DC-link connection, connection for
braking resistor
DCP/R1, DCN, R2
3)
Without line filter
kg
1,4
1,4
1,8
Rated output of a typical standard induction motor at 230 V.
The input current depends on th
e motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
Max. motor cable length 50 m (shielded) for PM240-2 Power Modules with integrated line filter to maintain the limit
values of EN 61800-3 Category C2.
4)
Power loss in the cabinet: 0.02 kW. The remaining power loss is dissipated via the heat sink.
Table 4- 9 Technical data of the PM240-2, FSB (200 V)
Line voltage 1-phase/3-phase 200 … 240 VAC ± 10%
Order number
without integrated line filter
with integrated line filter
6SL3210–
1PB15-5UL0
1PB15-5AL0
6SL3210–
1PB17-4UL0
1PB17-4AL0
6SL3210–
1PB21-0UL0
1PB21-0AL0
6SL3211–
1PB21-0UL0
1PB21-0AL0
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
max
A
A
A
5,5
3,9
6,1
7,4
5,5
8,2
10,4
7,4
11,5
10,4
7,4
11,5
1)
based on I
n
kW
kW
1,1
0,75
1,5
1,1
2,2
1,5
2,2
1,5
4)
3