Power Modules
4.2 Blocksize Power Modules (PM240-2)
AC Drive
108 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Line voltage 1-phase/3-phase 200 … 240 VAC ± 10%
Order number
without integrated line filter
with integrated line filter
6SL3210–
1PB15-5UL0
1PB15-5AL0
6SL3210–
1PB17-4UL0
1PB17-4AL0
6SL3210–
1PB21-0UL0
1PB21-0AL0
6SL3211–
1PB21-0UL0
1PB21-0AL0
2)
with/without integrated line reactor
A 13,5 18,1 24,0 24,0
Rated current
Short-circuit current rating
A
20
25
35
35
3NE 1814-0
3NE 1815-0
3NE1803-0
3NE 1803-0
of the external
Ω ≥ 68 ≥ 68 ≥ 68 ≥ 68
Max. cable length
to braking resistor
Line supply connection L1, L2, PE
Screw-type terminals
cable cross-section: 1.5 … 6 mm
2
Tightening torque: 0.6 Nm
Motor connection U2, V2, W2
DC-link connection, connection for
braking resistor
DCP/R1, DCN, R2
On line connector
3)
Without line filter
kg
2,9
2,9
2,9
3,4
Rated output of a typical standard induction motor at 230 V.
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
Max. motor cable length 50 m (shielded) for PM240-2 Power Modules with integrated line filter to maintain the limit
values of EN 61800-3 Category C2.
4)