Power Modules
4.3 Power Modules Blocksize (PM340)
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
151
PM340 with integrated line filter
A 1,0 1,0 1,0
2)
with/without integrated line reactor
Rated current
Short-circuit current rating SCCR
A
3NE1817-0
50
3NE1818-0
60
3NE1820-0
90
3NA3820
3NA3822
3NA3824
Circuit-breaker type designation IEC
60947
3RV1042-4JA10
3RV1042-4KA10
3RV1042-4MA10
of the external braking resistor
Ω > 27 > 27 > 27
m 15 15 15
L1, L2, L3
Stud M6,
connectable cable cross-sections 10 ... 50 mm
2
DC link connection, connection for
braking resistor
At the housing with M6 screw
3)
PM340 with/without integrated line
mm (inch)
418,3 (16.47) / 511
418,3 (16.47) / 511
418,3 (16.47) / 511
with/without integrated line filter
Rated power of a typical standard induction motor at 400 V 3 AC
The input current depends on the motor load and line
impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
Max. motor cable length 25 m (shielded) for PM340 Power Modules with integrated line filter to maintain the limit values
of EN 61800-3 Category C2.