Power Modules
4.3 Power Modules Blocksize (PM340)
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
151
PM340
6SL3210-
1SE23-8UA0
1SE24-5UA0
1SE26-0UA0
PM340 with integrated line filter
6SL3210-
1SE23-8AA0
1SE24-5AA0
1SE26-0AA0
24 V DC supply
for the Control Unit
A 1,0 1,0 1,0
Rated input current
2)
with/without integrated line reactor
A
40 / 46
47 / 53
63 / 72
Class J UL fuses
Rated current
Short-circuit current rating SCCR
A
kA
3NE1817-0
50
65
3NE1818-0
60
65
3NE1820-0
90
65
NH fuses
IEC 60947
Rated current
A
3NA3820
50
3NA3822
63
3NA3824
80
Circuit-breaker type designation IEC
60947
rated current
A
3RV1042-4JA10
45 … 63
3RV1042-4KA10
57 … 75
3RV1042-4MA10
80 … 100
Resistance value
of the external braking resistor
Ω > 27 > 27 > 27
Max. cable length
to braking resistor
m 15 15 15
Line supply connection
L1, L2, L3
Stud M6,
connectable cable cross-sections 10 ... 50 mm
2
Motor connection
U2, V2, W2
DC link connection, connection for
braking resistor
DCP/R1, DCN, R2
PE connection
At the housing with M6 screw
Max. motor cable length
3)
shielded/unshielded
m
70 / 100
Degree of protection
IP20 or IPXXB
Height
PM340 with/without integrated line
filter
mm (inch)
418,3 (16.47) / 511
(20.11)
418,3 (16.47) / 511
(20.11)
418,3 (16.47) / 511
(20.11)
Weight
with/without integrated line filter
kg
15,9 / 19,3
15,9 / 19,3
15,9 / 19,3
1)
Rated power of a typical standard induction motor at 400 V 3 AC
2)
The input current depends on the motor load and line
impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
3)
Max. motor cable length 25 m (shielded) for PM340 Power Modules with integrated line filter to maintain the limit values
of EN 61800-3 Category C2.

Table of Contents

Other manuals for Siemens S120