Supplementary system components and encoder system integration
8.1 Sensor Modules
AC Drive
364 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
X521 / X531 alternative encoder system interface
Table 8- 14 X521/X531: Alternative encoder system interface
X521
X531
Inverse incremental signal A
Inverse incremental signal B
Inverse reference signal R
Ground, encoder power supply
3 - Temp
1)
Motor temperature sensing KTY84-1C130 (KTY-)
Temperature sensor KTY84-1C130 / PTC
4 + Temp
1)
Motor temperature sensing KTY84-1C130 (KTY+)
Temperature sensor KTY84-1C130 / PTC
8 Data* Inverse SSI data
Max. connectable cross-section: 1.5 mm
2
Measuring current via the temperature sensor connection: 2 mA
When unipolar HTL encoders are used, A*, B*, and R* on the terminal block must be jumpered with M_Encoder (X531)
2)
Accuracy of temperature measurement:
- KTY: ±7°C (including evaluation)
- PTC: ±5℃ (including evaluation)
Because the physical transmission media is more robust, the bipolar connection should always be used. The unipolar
connection should only be used if the encoder type does not output push-pull signals.
Danger to life through electric shock due to unconnected cable shields
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
• Attach the cable shield to the component for the encoder system connection at the
terminals.