Mains connection and line-side power components
3.8 Line reactors
AC Drive
74 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Table 3- 20 Technical data, Blocksize line reactors PM340, frame sizes FSB and FSC
Line voltage 3-phase 380 VAC -10% to 480 VAC +10%
Suitable for
Power Module
1SE16-0xxx
1SE17-7xxx
1SE21-0xxx 1SE21-8xxx
1SE22-5xxx
1SE23-2xxx
Power loss
W 9 / 11 27 / 32 98 / 118 37 / 44
Line supply
connection
Screw-type terminal
6 mm
2
Screw-type terminal
6 mm
2
Screw-type terminal
6 mm
2
Screw-type terminal
6 mm
2
Load connection
1U2, 1V2, 1W2
Cable 4 x 1.5 mm
2
Length approx. 0.46
Cable 4 x 1.5 mm
2
Length approx. 0.46
Cable 4 x 2.5 mm
2
Length approx. 0.49
Cable 4 x 2.5 mm
2
Length approx. 0.49 m
PE connection At the housing with
At the housing with
At the housing with
At the housing with