Parameter 7749 or 7750 – to recover base software and restore current DCR state
1. To save current parameter con󹪝guration and current SOP:
from ToolSuite Drive Tool Host, Con󹪝guration → Save As to save current con󹪝guration
parameter 󹪝le to your PC.
from ToolSuite Drive Tool Host, Con󹪝guration → System Program à Upload System
Program to save current SOP 󹪝le to your PC.
2. On a PC, remove all secure USB key 󹪝les from USB 󹪞ash disk OR rename them.
3. Insert FAT32-based USB 󹪞ash disk into DCR.
4. Generate nxgrecover.factory key via keypad parameter 7749 OR nxgrecover key via keypad
parameter 7750.
The 󹪝le should be created within 30 seconds.
ONLY one type should be created.
You can remove the USB 󹪞ash disk, insert into PC to check 󹪝le creation. If trying to recover,
then re-insert into DCR
5. STOP HERE IF YOU ARE ONLY CREATING THE KEYS
CAUTION
STOP HERE IF YOU ARE ONLY CREATING THE KEYS
STOP HERE IF YOU ARE ONLY CREATING THE KEY; REMOVE USB FLASH DISK. PROCEEDING
WILL RESET YOUR DCR AND ERASE ALL SAVED PARAMETERS ON DCR.
6. Reboot DCR (leave USB 󹪞ash disk inserted).
Wait approximately 5-7 minutes for Green LED blink 7x repeatedly.
If it does not (e.g. Red LED blink 15x repeatedly), recover FAILED.
If the DCR boots up normally and you can connect via Drive Tool or Debug Tool, then the
USB 󹪞ash drive was not recognized. Try another brand and/or model.
1. Remove USB 󹪞ash disk from DCR.
2. Reboot DCR.
3. After ~60-90 seconds, you should be able to connect using Drive Tool and Debug Tool using
default IP con󹪝guration.
4. Now you will be able to reload customer-speci󹪝c parameter con󹪝guration 󹪝le and SOP 󹪝le
from your PC.
5. Then reboot DCR again.
Software user interface
9.4 Security Measures
NXGPro+ Control Manual
Operating Manual, A5E50491925A 399

Table of Contents