Line Connection Booksize
2.10 Line reactors for Active Line Modules
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
101
2.10.3 Connection description
Figure 2-34 Line reactor (example: 16 kW)
2.10.3.1 Line/power connection
Table 2-32 Connection types for line reactors
Terminals Designations
Line supply connection 1U1, 1V1, 1W1, PE
Load connection 1U2, 1V2, 1W2
Line reactors for Active Line Modules
16 kW Screw terminal 16 mm
2
3–pin/6 Nm*
36 kW Screw terminal 35 mm
2
3–pin/6 Nm*
55 kW Screw terminal 70 mm
2
3–pin/6 Nm*
80 kW Connecting lug d = 9 mm (M10/25 Nm) for ring cable lug acc. to DIN 46234
Note: No shock-hazard protection (IP00B acc. to 60529)
120 kW Connecting lug d = 10 mm (M10/25 Nm) for ring cable lug acc. to DIN 46234
Note: No shock-hazard protection (IP00B acc. to 60529)
*
See Chapter Screw terminals