Line Modules Booksize
3.7 Smart Line Modules Booksize Compact
Booksize power units
290 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
3.7.7 Technical data
Table 3-59 Technical data for Smart Line Modules in Booksize Compact format
Smart Line Module Booksize Compact 6SL3430– 6TE21-6AAx
Rated power kW 16
Infeed:
Rated power (S1)
1)
S6 infeed
Power rating (S6-40%)
1)
Peak power rating
1)
kW (Pn)
kW (Ps6)
kW (Pmax)
16
21
35
Regenerative feedback:
Continuous regenerative power rating
Peak regenerative power rating
kW
kW
16
35
Line supply voltages:
Line voltage
Line frequency
Electronics power supply
V
AC
Hz
V
DC
380 3 AC -10 % (-15 % < 1 min) up to 480 3 AC +10 %
47 to 63
24 (20.4 - 28.8)
DC link voltage
Overvoltage trip threshold
Undervoltage trip threshold
V
DC
V
DC
V
DC
510 – 720
820 ± 2 %
360 ± 2 %
Input current:
Rated current at 380 V
AC
at 480 V
AC
/528 V
AC
at 480 V; S6 duty (40 %)
Peak current
A
AC
A
AC
A
AC
A
AC
26
21/19
35
59
DC link current:
At 600 V DC
at S6 duty (40 %)
peak current
A
DC
A
DC
A
DC
27
35
59
DC link busbar current carrying capacity A
DC
100
24 V busbar current carrying capacity A
DC
20
Current consumption of electronics for internal air
cooling
A
DC
1.1
Current consumption of electronics for cold-plate
cooling
A
DC
0.9
Total power loss internal air cooling
(including electronic losses)
2)
W 191.4
Power loss distribution for cold plate (including
electronics losses)
Internal
External
W
56.6
130
Max. ambient temperature without derating °C 40
Max. ambient temperature with derating °C 55
DC link capacitance μF 705
Maximum permissible DC link capacitance μF 6000
Power factor cos ϕ 0.98