EasyManua.ls Logo

Siemens SINAMICS S120 - Technical Data

Siemens SINAMICS S120
570 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Line Modules Booksize
3.7 Smart Line Modules Booksize Compact
Booksize power units
290 Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
3.7.7 Technical data
Table 3-59 Technical data for Smart Line Modules in Booksize Compact format
Smart Line Module Booksize Compact 6SL3430– 6TE21-6AAx
Rated power kW 16
Infeed:
Rated power (S1)
1)
S6 infeed
Power rating (S6-40%)
1)
Peak power rating
1)
kW (Pn)
kW (Ps6)
kW (Pmax)
16
21
35
Regenerative feedback:
Continuous regenerative power rating
Peak regenerative power rating
kW
kW
16
35
Line supply voltages:
Line voltage
Line frequency
Electronics power supply
V
AC
Hz
V
DC
380 3 AC -10 % (-15 % < 1 min) up to 480 3 AC +10 %
47 to 63
24 (20.4 - 28.8)
DC link voltage
Overvoltage trip threshold
Undervoltage trip threshold
V
DC
V
DC
V
DC
510 – 720
820 ± 2 %
360 ± 2 %
Input current:
Rated current at 380 V
AC
at 480 V
AC
/528 V
AC
at 480 V; S6 duty (40 %)
Peak current
A
AC
A
AC
A
AC
A
AC
26
21/19
35
59
DC link current:
At 600 V DC
at S6 duty (40 %)
peak current
A
DC
A
DC
A
DC
27
35
59
DC link busbar current carrying capacity A
DC
100
24 V busbar current carrying capacity A
DC
20
Current consumption of electronics for internal air
cooling
A
DC
1.1
Current consumption of electronics for cold-plate
cooling
A
DC
0.9
Total power loss internal air cooling
(including electronic losses)
2)
W 191.4
Power loss distribution for cold plate (including
electronics losses)
Internal
External
W
56.6
130
Max. ambient temperature without derating °C 40
Max. ambient temperature with derating °C 55
DC link capacitance μF 705
Maximum permissible DC link capacitance μF 6000
Power factor cos ϕ 0.98