3.6.7 Technical data
Table 3-52 Technical data for Booksize Smart Line Modules with internal air cooling
Internal air cooling 6SL3130– 6TE21-6ABx 6TE23-6ABx
Rated power kW 16 36
Infeed:
Rated power (S1)
1)
S6 infeed
Power rating (S6-40%)
1)
Peak power rating
1)
kW (Pn)
kW (Ps6)
kW (Pmax)
16
21
35
36
47
70
Regenerative feedback:
Continuous regenerative power rating
Peak regenerative power rating
kW
kW
16
35
36
70
Line supply voltages:
Line voltage
Line frequency
Electronics power supply
V
AC
Hz
V
DC
3-ph. 380 V AC -10% (-15% < 1 min) to 3-ph. 480 V
AC +10%
47 to 63
24 (20.4 - 28.8)
DC link voltage
Overvoltage trip threshold
Undervoltage trip threshold
V
DC
V
DC
V
DC
510 – 720
820 ± 2 %
360 ± 2 %
Rated input current:
at 380 V
AC
at 480 V
AC
/528 V
AC
at 480 V; S6-40%)
Peak current (at 400 V
AC
/480 V
AC
)
A
AC
A
AC
A
AC
A
AC
26
21/19
27
54 /45
58
46/42
60
107/89
DC link current:
Rated current
at S6-40%
Peak current
A
DC
A
DC
A
DC
27
35
59
60
79
117
DC link busbar current carrying capacity A
DC
100 100
24 V busbar current carrying capacity A
DC
20 20
Electronics current consumption A
DC
1.1 1.5
Total power loss
(including electronic losses)
2)
W 191.4 406
Max. ambient temperature without derating °C 40 40
Max. ambient temperature with derating °C 55 55
DC link capacitance μF 705 1410
Maximum permissible DC link capacitance μF 20 000 20 000
Power factor cos ϕ 0.98 0.98
Circuit-breaker type designation
(status 06/2007)
Rated current
Short-circuit current rating SCCR at 400 V
AC
A
kA
3RV1031-4FA10
28 ... 40
50
3RV1031-4LA10
70 ... 90
50